6.2 WIRING CONFIGURATIONS
Combining all the grounding and input type possibilities provides us with the follow-
ing potential connection configurations. The combinations along with our recommen-
dations on usage are shown in the chart below.
RecommendedDifferential Inputs
Already Isolated
Grounds
AcceptableSingle-ended Inputs
Already Isolated
Grounds
Unacceptable without
adding Isolation
Differential Inputs
Common Mode
Voltage > +/-10V
Unacceptable without
adding Isolation
Single-Ended Inputs
Common Mode
Voltage > +/- 10V
RecommendedDifferential Inputs
Common Mode
Voltage < +/-10V
Not RecommendedSingle-Ended Inputs
Common Mode
Voltage < +/-10V
AcceptableDifferential InputsCommon Ground
RecommendedSingle-Ended InputsCommon Ground