CB-7080 & CB-7080D Counter/Timer User's Guide ~AAAS
2-7
~AAAS
Description: Sets counter alarm mode. Refer to "Counter alarm mode selection" on page 1-7 for more
information.
Syntax: ~AAAS[chk](cr)
~ A delimiter character
AA 2-character HEX module address, from 00 to FF
S=0 alarm mode 0.
S=1 alarm mode 1.
[chk] 2-character checksum. If checksum is disabled no [chk]
(cr) 0x0D
Response:
Valid response !AA[chk](cr)
invalid response ?AA[chk](cr)
no response Syntax error, communication error or address error
! A delimiter character indicating a valid response
? A delimiter character indicating an invalid response
AA 2-character HEX module address
[chk] 2-character checksum. If checksum is disabled, no [chk].
(cr) 0x0D
Examples:
Set alarm mode=0.
command: ~01A0(cr)
response: !01(cr)
Set alarm mode=1.
command: ~02A1(cr)
response: !02(cr)