26
CB-7013, CB-7033 Users Manual
2.9 $AA8
Description: Read LED Configuration
Note: This command is for CB-7013D/CB-7033D only.
Syntax: $AA8[CHK](cr)
$ delimiter character
AA address of reading module (00 to FF)
8 command for set LED configuration
Response: Valid Command: !AAV[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
V LED configuration
For CB-7013D, 1=module control, 2=host control
For CB-7033D, 0~2=LED show channel 0~2,
3=LED is host control
Example:
Command: $018 Receive: !011
Read address 01 LED configuration, return 1.
Command: $028 Receive: !012
Read address 02 LED configuration, return 2
Related Command:
Sec. 2.10 $AA8V, Sec. 2.11 $AA9(Data)