Measurement-computing CB-COM-7013 Manuale Utente Pagina 27

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 44
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 26
27
CB-7013, CB-7033 Users Manual
2.10 $AA8V
Description: Set LED Configuration
Note: This command is for CB-7013D/CB-7033D only.
Syntax: $AA8V[CHK](cr)
$ Delimiter character.
AA Address of setting module (00 to FF).
8 Command for set LED configuration.
V For CB-7013D, 1=Set LED to module, 2=Set LED to
host.
For CB-7033D, 0~2=Set LED to show channel 0~2
3=Set LED to host.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command.
? Delimiter for invalid command.
AA Address of response module (00 to FF).
Example:
Command: $0180 Receive: !01
Set address 01 LED to 0, return successful
Command: $0281 Receive: !02
Set address 02 LED to 1, return successful
Related Command:
Sec. 2.9 $AA8, Sec. 2.11 $AA9(Data)
Vedere la pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 43 44

Commenti su questo manuale

Nessun commento