DAQFlex Software User's Guide DAQFlex Message Reference Reflection messages AO
81
SRCS
Set the edge trigger type.
Message
"@AITRIG:SRCS"
Response
"AITRIG:SRCS=implementation>value"
implementation
FIXED%, PROG% (programmable), HWSEL% (hardware selectable),
or not specified if value is NOT_SUPPORTED
value
HW/DIG, HW/ANLG, or returns NOT_SUPPORTED if the device
doesn't support triggering analog input scans.
Example
"AITRIG:SRCS=PROG%HW/DIG,HW/ANLG"
TYPES
Get the types of trigger sensing that are supported by the device.
Message
"@AITRIG:TYPES"
Response
"AITRIG:TYPES=implementation>value"
implementation
FIXED%, PROG% (programmable), HWSEL% (hardware selectable),
or not specified if value is NOT_SUPPORTED
value
<type>/<condition> or returns NOT_SUPPORTED if the device
doesn't support triggering analog input scans.
type
EDGE, LEVEL
condition
RISING, FALLING, if type is EDGE.
HIGH, LOW if type is LEVEL.
Example
"AITRIG:TYPES=PROG%EDGE/RISING,EDGE/FALLING"
AO
Gets the analog output properties of a device.
Properties
CHANNELS, FACCAL, MAXCOUNT, MAXRATE, OUTPUTS, RANGES, SELFCAL
CHANNELS
Get the number of analog output channels on a device.
Message
"@AO:CHANNELS"
Response
"AO:CHANNELS=<implementation>value"
implementation
FIXED%, PROG%, or not specified if value is NOT_SUPPORTED
value
The number of D/A channels on a device, or returns
NOT_SUPPORTED if the device doesn’t support analog output.
Example
"AO:CHANNELS=FIXED%4"