CB-7000 DIO Manual
2.5 $AA2
Description: Read Configuration
Command: $AA2[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
2 Command for read configuration
Response: Valid Command:
!AATTCCFF[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid Command
? Delimiter for invalid Command
AA Address of response module(00 to FF)
TT Type code of module; it must be 40
CC Baud rate code of module (Ref. Sec. 1.9)
FF Data format of module (Ref. Sec. 1.9)
Example:
Command: $012 Receive: !01400600
Read Address 01 status, return DIO mode, baud 9600, no
checksum.
Related Command:
Sec. 2.1, %AANNTTCCFF
Related Topics:
Sec. 1.9, Configuration Tables; Sec. 3.1, INIT* pin Operation