CB-7000 DIO Manual
Reset the host watchdog timer.
Wait for about 10 seconds and don’t send command ~**, the LED
of module will flash. The flashing LED indicates the host watch-
dog timeout status is set.
Command: ~010 Receive: !0104
Read Address 01 modul status, return host watchdog timeout
status is set.
Command: ~012 Receive: !01064
Read Address 01 host watchdog timeout value, return that host
watchdog is disabled, and time interval is 10.0 seconds.
Command: ~011 Receive: !01
Reset Address 01 host watchdog timeout status, return suc-
cessful. And the LED of this module stop flash.
Command: ~010 Receive: !0100
Read Address 01 module status, return host watchdog timeout
status is clear.
Related Command:
Sec. 2.17, ~**; Sec. 2.18, ~AA0; Sec. 2.19, ~AA1; Sec. 2.20, AA2;
Sec. 2.22, ~AA4V; Sec. 2.23, ~AA5V
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation