Measurement-computing CB-7000 DIO Manuale Utente Pagina 53

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 68
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 52
53
CB-7000 DIO Manual
2.22 ~AA4V
Description: Read PowerOn/Safe Value.
Command: ~AA4V[CHK](cr)
~ Delimiter character
AA Address of reading module (00 to FF)
4 Command for read PowerOn/Safe Value
V P = read PowerOn value, S = read Safe Value
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid Command
? Delimiter for invalid Command
AA Address of response module(00 to FF)
(Data) PowerOn Value or Safe Value
For CB-7042/42D/43/43D (Data) is VVVV, where
VVVV is the PowerOn Value (or Safe Value).
For other modules, (Data) is VV00, where VV is the
PowerOn Value(or Safe Value).
Example:
Command: @010000 Receive: >
Output Address 01 value 0000, return successful.
Command: ~015S Receive: !01
Set Address 01 Safe Value, return successful.
Command: @01FFFF Receive: >
Output Address 01 value FFFF, return successful.
Command: ~015P Receive: !01
Vedere la pagina 52