2.7 $AA5
Description: Read Reset Status
Command: $AA5[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
5 Command for read reset status
Response: Valid Command: !AAS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid Command
? Delimiter for invalid Command
AA Address of response module(00 to FF)
S Reset status, 1 = the module has been reset,
0 = the module has not been reset.
Example:
Command: $015 Receive: !011
Read Address 01 reset status, return first read.
Command: $015 Receive: !010
Read Address 01 reset status, return no reset occurred.