CB-7021, CB-7022, CB-7024 Users Manual
DA Configuration of CB-7022
Analog Output Type (T)
0 0 mA to 20 mA current output
1 4 mA to 20 mA current output
2 0V to 10V voltage output
Slew Rate Control (S)
0 Immediate change
1 0.0625V/Second or 0.125 mA/Second
2 0.125V/Second or 0.25 mA/Second
3 0.25V/Second or 0.5 mA/Second
4 0.5V/Second or 1.0 mA/Second
5 1.0V/Second or 2.0 mA/Second
6 2.0V/Second or 4.0 mA/Second
7 4.0V/Second or 8.0 mA/Second
8 8.0V/Second or 16 mA/Second
9 16V/Second or 32 mA/Second
A 32V/Second or 64 mA/Second
B 64V/Second or 128 mA/Second
C 128V/Second or 256 mA/Second
D 256V/Second or 512 mA/Second
E 512V/Second or 1024 mA/Second