Measurement-computing CB-COM-7021 Manuale Utente Pagina 67

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 76
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 66
67
CB-7021, CB-7022, CB-7024 Users Manual
2.33 ~AA5N
Description: Set Safe Value of Channel N
Note: The command is for CB-7022 and CB-7024 only.
Command: ~AA5N[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
5 Command to store current output as Safe Value
N Channel to set (0 to 1 for CB-7022, 0 to 3 for CB-7024)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may not get a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example for CB-7024:
Command: #010+05.000 Receive: !01
Output address 01 channel 0 value +5.0, returns successful.
Command: ~0150 Receive: !01
Set address 01 channel 0 Safe Value, returns successful.
Related Command:
Sec. 2.25, ~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2;
Sec. 2.29, ~AA3EVV; Sec. 2.31, ~AA4N
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
Vedere la pagina 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72 ... 75 76

Commenti su questo manuale

Nessun commento