CB-7021, CB-7022, CB-7024 Users Manual
2.21.2 $AA7N
Description: Read PowerOn Value of Channel N
Note: The command is for CB-7024 only.
Syntax: $AA7N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
7 Command for reading PowerOn Value
N Channel to readback (0 to 3)
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Last output command value. See Sec. 1.9 for the
format.
Example:
Command: $0170 Receive: !01+00.000
Read address 01 channel 0 PowerOn Value, returns +10.0.
Related Command:
Sec. 2.19, $AA4N