54
CB-7021, CB-7022, CB-7024 User’s Manual
2.22 $AA8N
Description: Current Value of Channel N Readback
Note: The command is for CB-7022 and CB-7024 only.
Syntax: $AA8N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
8 Command for read current output value
N Channel to readback (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Last output command value. See Sec. 1.9 for format.
Example for CB-7024:
Command: $012 Receive: !01320614
Read address 01 configuration, returns output type 0 to 10V,
9600 bps, engineer unit format and slew rate is 1.0V/Second.
Command: #010+10.000 Receive: !01
Set address 01 channel 0 output 10.0V, returns successful.
Command: $0160 Receive: !01+10.000
Read address 01 channel 0 last output command value, re-
turns 10.000.
Commenti su questo manuale