Measurement-computing CB-COM-7012 Manuale Utente Pagina 23

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 72
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 22
23
CB-7012, CB-7014, CB-7017 Users Manual
2.1 %AANNTTCCFF
Description: Set Module Configuration
Syntax: %AANNTTCCFF[CHK](cr)
% a Delimiter character
AA Address of module to set (00 to FF)
NN new Address for module to set (00 to FF)
TT new type for module to set (Ref. Sec. 1.10)
CC new baudrate for receiving module (Ref. Sec. 1.10). Short
INIT* to ground when changing baudrate. (Ref. Sec. 3.1)
FF New data format for module (Ref. Sec. 1.10).
Short INIT* to ground when changing checksum setting.
(Ref. Sec. 3.1)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command. If you change baud
rate or checksum setting without shorting INIT* to ground,
the module will return an invalid command.
AA Address of responding module (00 to FF)
Example:
Command: %0102080600 Receive: !02
Change Address from 01 to 02, return successful.
Command: %0202080602 Receive: !02
Change data format from 00 to 02, return successful.
Vedere la pagina 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 71 72

Commenti su questo manuale

Nessun commento