Measurement-computing CB-COM-7012 Manuale Utente Pagina 48

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 72
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 47
48
CB-7012, CB-7014, CB-7017 Users Manual
2.25 @AACA
Description: Clear Latch Alarm
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: @AACA[CHK](cr)
@ Delimiter character
AA Address of module to set (00 to FF)
CA Command for clear latch alarm
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: @01DI Receive: !0120101
Read Address 01 digital input, return latch alarm mode, low
alarm active.
Command: @01CA Receive: !01
Clear Address 01 latch alarm, return successful.
Command: @01DI Receive: !0120001
Read Address 01 digital input, return latch alarm mode, no
alarm active.
Related Command:
Sec. 2.19, @AADI; Sec. 2.21, @AAEAT; Sec. 2.24, @AADA
Related Topic:
Sec. 3.6 High/Low Alarm
Vedere la pagina 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 71 72

Commenti su questo manuale

Nessun commento