31
CB-7012, CB-7014, CB-7017 User’s Manual
2.8 $AA4
Description: Read Synchronized Data
Syntax: $AA4[CHK](cr)
$ Delimiter character
AA Address of module (00 to FF)
4 Command for reading synchronized data
Response: Valid Command: >AAS(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
S Status of synchronized data, 1 = first read, 0 = been read
(Data) Synchronized data, format reference Sec. 1.10
Example:
Command: $014 Receive: ?01
Read Address 01 synchronized data, return no valid data.
Command: #** Receive: no response
Preform synchronized sampling
Command: $014 Receive: >011+02.556
Read Address 01 synchronized data, return status 1 and data.
Command: $014 Receive: >010+02.556
Read Address 01 synchronized data, return status 0 and data.
Related Command:
Sec. 2.2, #**
Note: This command is for CB-7012/12D/12F/12FD/14D only.