CB-7012, CB-7014, CB-7017 Users Manual
2.30 $AA3
Description: Read Source Low/High Values for Linear Mapping
Note: This command is for CB-7014D only.
Syntax: $AA3[CHK](cr)
$ Delimiter character
AA Address of module (00 to FF)
3 Command for reading source values
Response: Valid Command: !AA(SL)(SH)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
SL Low limit of source values in engineering unit format.
SH High limit of source values in engineering unit format.
Example:
Command: $013 Receive: !01-10.000+10.000
Read Address 01 source value, return from -10 to +10.
Related Command:
Sec. 2.31, $AA5; Sec. 2.32, $AA6(SL)(SH); Sec. 2.33,
$AA7(TL)(TH)
Related Topic:
Sec. 3.8, Linear Mapping