38
CB-7012, CB-7014, CB-7017 Users Manual
2.15 $AAF
Description: Read Firmware Version
Syntax: $AAF[CHK](cr)
$ Delimiter character
AA Address of module (00 to FF)
F Command for read firmware version
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
(Data) firmware version of module
Example:
Command: $01F Receive: !01A2.0
Read Address 01 firmware version, return version A2.0.
Command: $02F Receive: !01B1.1
Read Address 02 firmware version, return version B1.1.