Measurement-computing CB-COM-7012 Manuale Utente Pagina 56

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 72
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 55
56
CB-7012, CB-7014, CB-7017 Users Manual
2.33 $AA7(TL)(TH)
Description: Set Target Low/High Values for Linear Mapping
Note: The command is for CB-7014D only.
This command must follow the $AA6(SL)(SH) command.
Syntax: $AA7(TL)(TH)[CHK](cr)
$ Delimiter character
AA Address of module to set (00 to FF)
7 Command for setting target values
TL target low level value in engineering unit format
TH target high level value in engineering unit format
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: $07610.000+10.000 Receive: !01
Set Address 01 target value 10 to +10, return successful.
Related Command:
Sec. 2.30, $AA3; Sec. 2.31, $AA5; Sec. 2.32, $AA6(SL)(SH)
Related Topic:
Sec. 3.8, Linear Mapping
Vedere la pagina 55
1 2 ... 51 52 53 54 55 56 57 58 59 60 61 ... 71 72

Commenti su questo manuale

Nessun commento