CB-7012, CB-7014, CB-7017 Users Manual
2.14 $AAA
Description: Read eight channel of data
Note: The command is for CB-7017/17F only.
Syntax: $AAA[CHK](cr)
$ Delimiter character
AA Address of module (00 to FF)
A Command for reading eight channels of analog input data
Response: Valid Command:
>(Data1)..(Data8)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
(Data1)...(Data8) 8 channel analog input data, in 2’s complement
HEX format.
Example:
Command: $01A
Receive: >0000012301257FFF1802744F98238124
Read Address 01 8-channel analog input data, return
successful.
Related Command:
Sec. 2.3, #AA